Part Number Hot Search : 
TA7411AP 40T03GJ 64571 B65287 RF5604SB 1N5254 Z5234 0RNBSAC
Product Description
Full Text Search
 

To Download TPSRM24150 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Contact Factory for Replacement Model
Input Specifications
Parameter
Operating Range Current Efficiency Power Factor Correction (PFC)
Conditions
45 - 65 Hz, single phase, no taps required Adjustable
Min
183
Typ
Max
264 27 >85 >.99
Units
VAC A %
MEASUREMENTS OF RM24150
Module Weight Height Depth Width Shelf* Weight Height Depth Width 25 lbs. 7U (12.25") 15.25" 5.1" 18 lbs. 7U (12.25") 15..25" maximum 23" rack mount
*These measurements are specifically for the 600A Power Shelf for up to 4 quantity RM24150. Please consult factory for other shelf and power plant options.
GENERAL FEATURES
Hot Swappable Modules These shelf-mounted modules are easy and safe to install or remove while system is operational without affecting the overall system's performance. Parallel Operation and Automatic Load Sharing Forced or passive load sharing is available between modules of the same operating voltages in parallel applications. Current Limit The Current Limit is adjustable between 0A to 150A. Upon exceeding this limit, the rectifier automatically reduces output voltage. Safety UL/CUL Recognized: UL 1950/CSA 950 File Number: E181908.
Alarm Outputs Rectifier Fail Alarm Thermal Shutdown Occurring Open Sense Lead Has Occurred AC Power Has Failed Alarm DC Breaker Is Open Alarm AC Breaker Is Open Alarm (RFA) (THSD) (OS) (ACF) (DCBKR) (ACBKR)
Control Inputs High Voltage Shutdown Restart Equalize Temporary Restraint Emergency Shutdown (HVSD) (RS) (EQ) (TR) (EMSD)
}
}
All control inputs are initiated with a ground closure 24VAC voltage reference to ground
Note: All alarms are "Form A" relay type contacts
Page 2
A4RM24150 5/98 REV A
Output Specifications
Parameter
Voltage Adjustment Range float voltage equalize voltage Regulation Load Current Hold-Up Time Filtering Voice band Wide band noise ENVIRONMENTAL Temperature Operating Storage Humidity Altitude Heat Dissipation Audible Noise non-condensing -0 +32 -50 -58 0 0 0 2440 <55 +50 122 +85 185 95 7000 2133 C F C F % ft. m Btu/hr dBa @ 20MHz 0-100% load within specified input voltage and frequency range within a 10 - 100% rating nominal AC line >16 < 32 <350 24 24 0.5 10 28 30 VDC VDC % % mS dBrnc mV p-p
Conditions
Min
Typ
Max
Units
@27V 5 ft. from any vertical surface
PROTECTION, ALARM AND CONTROL SYSTEMS
Rectifier Failure Alarm (RFA) Problems occurring because of an unacceptable relationship between the output power and load conditions will cause a Rectifier Failure Alarm (RFA). This alarm consists of a red LED and a flashing green OK LED. Conditions which may lead to an RFA are: Low Current - Output current has decreased to below 5% of its rated value. Unit Shutdown - Any shutdown occurrence due to overvoltage, external shutdown command, unacceptable ambient temperature conditions or low AC input voltage. Fan Malfunction - The fan has stopped operating or is not providing the airflow needed to cool the unit. Over Temperature - The ambient temperature has exceeded 50C. High Voltage Shutdown (HVSD) The unit's high voltage limit is adjustable up to 30VDC. When internal shutdown occurs, the unit may be restarted by a local switch or by a remote signal. Surge Protection The unit will withstand lightning and input surges of 6000V/3000A. Under Voltage Protection When input voltage is below 183 VAC, the rectifier's operation is automatically inhibited.
A4RM24150 5/98 REV A
Page 3
Mechanical
All measurements are in inches
Standard Options are shown, consult factory for other available options.
The information provided herein is believed to be reliable; however, C&D Technologies assumes no responsibility for inaccuracies or omissions. C&D Technologies assumes no responsibility for the use of this information, and all use of such information shall be entirely at the user's own risk. Prices and specifications are subject to change without notice. No patent rights or licenses to any of the circuits described herein are implied or granted to any third party. C&D Technologies does not authorize or warrant any C&D Technologies product for use in life support devices/systems or in aircraft control applications.
Page 4
A4RM24150 5/98 REV A


▲Up To Search▲   

 
Price & Availability of TPSRM24150

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X